Rigby Fire Extinguisher Service

We service portable fire extinguishers for businesses in Rigby, whether you have a single unit by the back door of an office or a full set of cylinders spread through a shop, restaurant or school building. The yearly visit is the core of it. We also handle the longer tests some cylinder types need, recharges after a discharge and new installations.

To book, call (208) 886-5401 or email idaho@1profire.com. A rough count of units by type helps us plan the visit. Not sure of the types? That's fine.

What happens at the yearly visit

Under NFPA 10, a certified technician does hands-on maintenance on each extinguisher once a year and records the work on a tag. The technician checks the gauge, pin, seal, hose and nozzle, looks over the cylinder for dents or corrosion, makes sure the label can be read, and confirms the unit is mounted where it belongs. A unit that fails comes out of service until it's fixed.

Longer tests by cylinder type

The date stamp on each cylinder shows what's due:

  • Stored-pressure dry chemical: an internal maintenance (a full teardown) every 6 years and a hydrostatic test every 12 years.
  • CO2, water and wet chemical (Class K): a hydrostatic test every 5 years, with no 6-year teardown.

If your building has both kinds on the wall, each cylinder runs on its own clock, so we check the stamps one by one during the annual visit.

Between our visits

Monthly checks are the owner's job. Once a month, someone on site should confirm that the gauge reads in the green, the pin and seal are in place, and nothing blocks the path to the unit. Our page on annual extinguisher certification in Rigby covers the tag in more detail, and if a unit has been used, even for a second, see extinguisher refill and recharge in Rigby.

Extinguishers for a new or changed space

International Fire Code Section 906 sets where portable extinguishers are required, based on the occupancy and the hazards inside, and it also covers placement and mounting. We match each unit to the fuel it will face:

  • Class A: ordinary combustibles such as wood, paper and cloth
  • Class B: flammable liquids
  • Class C: energized electrical equipment
  • Class D: combustible metals
  • Class K: cooking oils and fats

A kitchen with a hood suppression system also needs a Class K portable extinguisher. For a new building, a tenant change or a remodel, confirm the number and placement of units with the fire authority before anyone moves in. Once the units are hung and tagged, they join your annual schedule.

If your staff are expected to use the extinguishers, OSHA 29 CFR 1910.157(g) requires training when they're hired and at least once a year after that. Our page on fire extinguisher training in Rigby explains how it works.

Central Fire District and the code in Rigby

Idaho Code 41-253 makes the International Fire Code the statewide minimum, along with later editions the State Fire Marshal adopts. A State Fire Marshal bulletin put the 2018 IFC into effect on January 1, 2021, so ask which edition applies today before you lay out a new space. The City of Rigby gets its fire and emergency services from Central Fire District, which runs Station 1 in Rigby and keeps its headquarters at 697 Annis Hwy. Call the district when you have extinguisher questions about a new space or a commercial kitchen: how many units you need, where they go, and which office will inspect. State law gives code enforcement to the Idaho State Fire Marshal and the marshal's assistants.

Rigby and nearby towns

Our Rigby fire protection hub lists the other services we provide here. Managing more than one site? See fire extinguisher service in Ririe, fire extinguisher service in Menan and fire extinguisher service across Jefferson County.

Questions about extinguisher service in Rigby

How often do extinguishers in Rigby need service?

Once a year by a certified technician. Someone on site also does a quick visual check each month.

Who do I ask about extinguisher placement in a new Rigby space?

Start with Central Fire District, which provides fire services for the city. Ask them which office reviews and inspects businesses.

Does a unit that was only used for a second need a recharge?

Yes. Any discharge, even a short test squeeze, means the unit needs a recharge before it goes back on the wall.

Can you install extinguishers in a new building?

Yes. We pick the class for each hazard, mount and tag the units, and add them to your annual schedule.