NFPA 10 hydrostatic retests · 5-year and 12-year intervals · Title 19 licensed extinguisher service
Is your extinguisher due for a hydro test?
From across the room, most extinguishers look alike. Their test dates don't. A hydrostatic test fills the cylinder with water and pressurizes it to show the shell can still safely hold the pressure it works under. Your annual tag doesn't cover this. That tag records the yearly maintenance visit, and an extinguisher can carry a fresh annual tag while its hydrostatic date has already passed, which is exactly the kind of gap an inspector notices. Check both dates.
Five years or twelve: it depends on what's inside
NFPA 10 sets the hydrostatic interval by agent type:
- Every 5 years: carbon dioxide (CO2), water and wet chemical (Class K) extinguishers.
- Every 12 years: dry chemical extinguishers, including ABC multipurpose units.
Stored-pressure dry chemical units have one more date to track. At 6 years they get an internal maintenance, a full teardown that is a separate job from the pressure test. Keep the two on separate lines in your records.
Restaurants, watch the Class K unit. Any kitchen with a hood suppression system also needs a Class K portable extinguisher, and that unit is on the shorter 5-year cycle. The hood system itself is covered by our kitchen suppression service in San Bernardino County.
What happens during the test
The technician empties the extinguisher, removes the valve and looks inside the shell for corrosion or damage. Then the cylinder is filled with water. It's brought up to its test pressure and held there while the technician watches for leaks, bulging or permanent distortion. Fail means done. A failed shell is never repaired, so that extinguisher is replaced. A cylinder that passes is dried, recharged and reassembled, then goes back on its hanger with the new test date recorded on the unit.
Have an older unit? Ask us whether retesting or replacing it makes more sense before the work starts.
Who checks your extinguishers depends on your city
No single fire office covers the whole county. The San Bernardino County Fire Protection District's Office of the Fire Marshal handles inspections for many cities, among them Adelanto, Fontana, Grand Terrace, Hesperia, Needles, San Bernardino, Twentynine Palms, Upland and Yucca Valley. Some cities run their own. Rancho Cucamonga, for example, has its own fire district, with a Prevention Bureau under its own Fire Marshal.
Portable extinguishers fall under Section 906 of the California Fire Code, which the District adopts with local amendments, so confirm which edition applies to your building with your fire marshal. Not sure who covers your address? Start with the San Bernardino County Fire Office of the Fire Marshal.
Who does the work
California requires extinguisher service to be done by a firm and a technician licensed by the State Fire Marshal under Title 19. Our California work is done by Hedrick Fire Protection, which holds C-16 and C-10 contractor licenses and is licensed by the State Fire Marshal under Title 19 for extinguisher service and water-based system work.
San Bernardino County is in our service area, from the valley to the mountains and the desert. Call (909) 219-9411 or email socal@1profire.com. Tell us how many extinguishers you have. Types help too.
Related services and nearby cities
- Fire protection services in San Bernardino County
- Annual fire extinguisher service in San Bernardino County
- Fire extinguisher training for San Bernardino County staff
- Fire sprinkler inspection and service in San Bernardino County
- Hydrostatic testing in Fontana
- Hydrostatic testing in Rancho Cucamonga
- Hydrostatic testing in Big Bear Lake
For a high desert example of our extinguisher work, read about weatherproof extinguisher tags for a Victorville carnival.
Hydrostatic testing questions
Does my annual extinguisher inspection include the hydrostatic test?
No. The yearly visit is maintenance, and the hydro test runs on its own 5-year or 12-year schedule set by the extinguisher type.
How often does a CO2 extinguisher need a hydro test?
Every 5 years. Water and wet chemical (Class K) units are on that same 5-year cycle.
What happens if a cylinder fails?
It's taken out of service. A failed shell can't be repaired, so the extinguisher gets replaced.
Who is allowed to do hydrostatic testing in California?
Only a firm and a technician licensed by the State Fire Marshal under Title 19 may do it.
Get a hydrostatic testing quote in San Bernardino County
- 5-year retests for CO2, water and Class K units
- 12-year retests for dry chemical units
- Title 19 licensed extinguisher service