NFPA 25 inspection, testing & maintenance · Title 19 five-year certification · Dry-pipe systems

Sprinkler systems run on a calendar. In California that calendar has two layers: NFPA 25 sets the quarterly, annual and five-year inspection and test work, and Title 19 adds a five-year service and certification that only a State Fire Marshal licensed contractor can sign. We handle both for buildings across San Bernardino County.

What's due, and when

  • Quarterly: gauges, alarm devices and visible components.
  • Annual: a broader inspection and test of the whole system.
  • Every five years: an internal pipe assessment, plus gauge replacement or testing.
  • Every five years in California: the Title 19 service and certification.
  • At 50 years in service: replace the heads or sample-test them.

The five-year date is the one owners lose track of. An inspector reading your records sees when the last certification was signed, and if that date is more than five years old the system is behind, even when every head looks fine from the floor. Old heads get missed too.

Does your building need sprinklers at all?

Where the San Bernardino County Fire Protection District has jurisdiction, its District Fire Code requires sprinklers in buildings of 5,000 square feet or more. The state line is 12,000. Cities with their own fire agency may set different rules, so confirm the current requirement with your local fire marshal before you plan around either number. Once a building is sprinklered, the NFPA 25 calendar above applies.

Cold-weather systems in the mountains

Big Bear Lake sits around 6,750 feet. Winter temperatures there drop below freezing, and water standing in a wet-pipe system can freeze, crack fittings and leave a branch line dead when a fire starts. Buildings at elevation often use dry-pipe systems instead, where air pressure holds the valve closed until a head opens. Those systems get extra attention at each visit: the technician checks the dry valve, drains condensate from the low points and trip-tests the valve on the schedule NFPA 25 sets. Low points collect water. Drain them before the first hard freeze.

Which fire office looks at your records

That depends on the city. The County Fire Office of the Fire Marshal, based at 598 S. Tippecanoe Ave. in San Bernardino, does inspection and regulatory work for cities that include Adelanto, Fontana, Grand Terrace, Hesperia, Needles, San Bernardino, Twentynine Palms, Upland and Yucca Valley. Other cities run their own departments. Rancho Cucamonga, for example, has its own fire protection district, with a Prevention Bureau under its own Fire Marshal that runs high-hazard Fire Code inspections. Not sure who covers your address? Start with the San Bernardino County Fire Office of the Fire Marshal.

Who does the work

Our California work is done by Hedrick Fire Protection. Hedrick holds C-16 fire protection and C-10 electrical contractor licenses, and the California State Fire Marshal licenses it under Title 19 for inspection, testing and maintenance of water-based fire protection systems, including the five-year certification. To book a visit or ask what's due on your system, reach us at (909) 219-9411 or socal@1profire.com.

Other services and nearby cities

Sprinkler service questions

Can you inspect a system another contractor installed?

Yes. NFPA 25 work applies to the system as it was built, whoever put it in. If you have past inspection reports, send them so the technician knows where your calendar stands.

Will testing set off the alarm or shut the building down?

Usually not. Flow tests run through test and drain valves, so the heads on the ceiling stay closed, but some tests do send an alarm signal, so tell your monitoring company and your occupants before the visit.

What should we have ready for the technician?

Access, mostly. The technician needs to reach the riser, the control valves, any dry valve room and the test connections, which may mean keys to locked rooms or roof hatches.

How do I tell how old my sprinkler heads are?

Check the deflector. Most heads have a manufacture year stamped on them, and the technician can read it during the annual visit.