When your extinguisher is due for a hydro test
Every extinguisher cylinder has a hydrostatic test date. Dry chemical units are due every 12 years. CO2, water and wet chemical (Class K) units are due every 5 years. Stored-pressure dry chemical units also get a 6-year internal maintenance, a teardown and inside inspection, which falls halfway between hydro tests on a 12-year unit.
Finding the date on your unit
Start with the cylinder itself. On a unit that has never been tested, the manufacture date is usually stamped into the metal near the neck or on the bottom, or printed on the maker's label, and the first test is counted from that date. Once a unit has been tested, a separate hydrostatic test label on the shell shows the month and year. The yearly service tag is different. It records annual maintenance.
What happens during the test
A hydro test checks whether the shell can still hold pressure safely. The technician empties the unit, removes the valve and looks inside for corrosion or damage. Then the shell is filled with water and pressurized to its test pressure. A leak, bulge or distortion fails it. Failed shells are taken out of service. A shell that passes is dried, refilled with its agent, recharged and labeled with the test date.
The unit is out of service meanwhile. Ask when you book how your units will be handled and how long they'll be gone, so you can plan cover for those spots.
Hemet's yearly business inspection
The Hemet Fire Department's Fire Prevention Bureau runs an annual fire inspection program for every business in the city, and Hemet's local fire code amendments require non-dwelling buildings to be inspected at least once a year. Portable extinguishers fall under California Fire Code Section 906, which Hemet's municipal code adopts.
Most of the calls we get from Hemet are about fire extinguishers, and some of them start with a fire department notice that the units are out of date. If you get one, check each cylinder's test label and manufacture date, write down which units are past due, and have that list ready when you call.
Who may test your extinguishers
In California, extinguisher service has to be done by a firm and technician licensed by the State Fire Marshal under Title 19. Hedrick Fire Protection does our California work. It holds a C-16 contractor license and State Fire Marshal licensing for portable extinguisher service.
Related pages
- Fire protection services in Hemet
- Annual fire extinguisher certification in Hemet
- Fire extinguisher refill in Hemet
- Fire extinguisher service in Hemet
- Hydrostatic testing in Riverside County
- Hydrostatic testing in San Bernardino County
- Hydrostatic testing in San Diego County
Hydrostatic testing questions
Is an extinguisher over 12 years old still serviceable?
Often, yes. A dry chemical unit that's past its hydro date needs a new hydrostatic test before it can be recertified, and a shell that fails has to be replaced.
Do I need a refill or a full certification?
It depends on why the unit was flagged. A discharged unit needs a refill, and an expired yearly tag needs annual maintenance. If the cylinder is also past its hydro date, the hydro test comes first. An overdue shell shouldn't be recharged.
Can every extinguisher be hydro tested?
No. Disposable units, usually the retail kind with plastic valve heads, aren't built to be serviced and are replaced at the end of their life.
For hydrostatic testing in Hemet, call us at (951) 384-0323 or email us at socal@1profire.com