Start with the write-up
Most repairs start on paper. Someone found a problem. Maybe it came from your annual inspection, maybe from a correction notice left by a city fire inspector after a walk-through of the kitchen and dining room.
Inside Ventura city limits, the Ventura Fire Department runs fire safety inspections through its Fire Prevention Division, which you can reach at 805-658-4717 if you have questions about a notice. Send us the list. We go through it item by item and explain what each fix involves. Some items take one part. Others need the water off.
What usually fails in a restaurant system
Kitchens are rough on sprinklers.
- Loaded heads. Grease or paint on a head can keep it from opening when heat reaches it, so NFPA 25 calls for a new head in its place.
- Corrosion. Steam and moisture near dish stations and prep sinks eat at heads and fittings.
- Physical damage. Ladders, carts and tall racks bend heads and knock escutcheons loose.
- Leaks. A drip at a fitting or riser is a warning. Fix it early.
- Gauges and valves. Gauges that read wrong get replaced or tested, and a valve that won't open or close all the way gets repaired.
- Old heads. Heads that have been in service 50 years must be replaced or sample-tested under NFPA 25.
On the day of the repair
Replacement heads must match. A technician checks the type, the temperature rating and the response of the head being replaced, because a mismatched head in a kitchen can open too early or too late.
If the repair needs the water off, part or all of the building is unprotected until it's back on. Plan for that. Tell your staff, and if your system is monitored, let the alarm company know before work starts. After the repair, the system is put back in service and checked for leaks. Then the deficiency comes off your list.
The hood system is separate
Your hood has its own fire system. It's a wet chemical system, inspected every six months under NFPA 96 and NFPA 17A, and it needs a Class K extinguisher nearby; none of that is part of a sprinkler repair. Hedrick Fire Protection is licensed to install and service commercial kitchen hood suppression systems. See kitchen fire system service in Ventura or fire extinguisher service in Ventura for those.
Who does the work
California work for 1 Pro Fire is done by Hedrick Fire Protection. Hedrick holds C-16 (fire protection) and C-10 (electrical) contractor licenses and is licensed by the California State Fire Marshal under Title 19 for inspection, testing and maintenance of water-based fire protection systems, including the five-year certification.
Ventura is on our service list, harbor restaurants included. For a routine visit, see restaurant sprinkler inspections in Ventura or general fire sprinkler service in Ventura.
Not in the city? We also handle restaurant sprinkler repair in Los Angeles County and restaurant sprinkler repair in Orange County, and the Ventura fire protection services hub lists everything else we do in the city.
Call (213) 568-0188 or email socal@1profire.com with your address and the deficiency list. We'll take it from there.
Ventura restaurant sprinkler repair questions
How often do you service the Ventura area?
We book Ventura visits as they're needed. Call or email with your address, what's wrong and when the kitchen is quiet (before lunch prep, after close), and we'll find a time.
Can a greasy sprinkler head be cleaned?
Usually not. NFPA 25 calls for replacing heads loaded with grease or paint, since scrubbing one in place can damage the part that reacts to heat.
Who inspects restaurant sprinklers inside the City of Ventura?
The Ventura Fire Department's Fire Prevention Division does fire safety inspections in the city. The county fire department is separate.
Is the hood system part of the sprinkler repair?
No. The hood has its own wet chemical system with its own six-month schedule, and we service it as a separate job.