Skip to main content

Start with the city, then the hood

Are you opening a new kitchen, adding a hood, or moving into a space that used to be something else? Inside the City of Ventura, the Fire Prevention Division of the Ventura Fire Department reviews construction plans, and its fire inspectors do fire safety inspections. Call the division first. The number is (805) 658-4717.

Ask what they want to see for a kitchen hood suppression system, and whether an inspector will be there for the final test. Ventura's fire rules are in Chapter 14.10 of the San Buenaventura Municipal Code, which adopts the California Fire Code with local amendments. Editions change. Confirm which one applies to your permit before design starts.

What a new hood system includes

A pre-engineered wet chemical system is laid out from the appliances under the hood. What is each one? How big is it, and where does it sit? Those answers set the nozzle count and the agent tank size. A typical installation has these parts:

  • Discharge nozzles aimed at each cooking appliance, plus nozzles for the hood plenum and the exhaust duct.
  • A detection line with fusible links that melt at a set temperature and trip the system.
  • A manual pull station the cook can reach on the way out.
  • Automatic shutoff of gas or electric power to the cooking equipment when the system discharges.
  • An agent tank and control head mounted where a technician can reach them.

Moving a fryer later changes the coverage. Tell us about planned equipment early.

Replacing an old dry chemical system

UL 300 is the test standard for pre-engineered wet chemical systems that protect cooking appliances. Older dry chemical systems don't meet it. If the Fire Prevention Division tells you yours has to go, that is an installation job: the old cylinder and piping come out, and a UL 300 listed wet chemical system goes in, sized to the appliances you cook on today.

One more item. Every kitchen with a suppression system also needs a Class K portable extinguisher near the cook line; we cover that under fire extinguisher service in Ventura.

Service starts six months out

Install day sets the calendar. Under NFPA 96 and NFPA 17A, a commercial cooking suppression system is inspected every six months, and the metal-alloy fusible links are replaced at least that often, so your first service date comes six months after the system goes live. Those visits are covered on our fire kitchen service page for Ventura. If the building also has sprinklers over the dining room or kitchen, see restaurant sprinkler inspections in Ventura.

Who does the installation

1 Pro Fire's California work is done by Hedrick Fire Protection, which holds C-16 (fire protection) and C-10 (electrical) contractor licenses, is licensed to install and service commercial kitchen hood fire suppression systems, and is licensed by the California State Fire Marshal under Title 19 for extinguisher service and for water-based system inspection, testing and maintenance.

Ventura is in our service area. To scope an installation, call (213) 568-0188 or email socal@1profire.com. For our other services in the city, start at the Ventura fire protection hub, or see the wider Ventura County and Los Angeles County pages.

Ventura kitchen installation questions

Will you come to a hospital kitchen in Ventura?

Yes. Ventura is in our service area, and hospital and other institutional kitchens follow the same NFPA 96 rules for hood suppression as restaurants do.

How often do you work in the Ventura area?

Ventura is one of the areas we cover. Give us your opening date or construction schedule when you call, and we will plan the installation and inspection around it.

Who reviews kitchen plans in the City of Ventura?

The Ventura Fire Department's Fire Prevention Division reviews construction plans and does fire safety inspections. Reach it at (805) 658-4717.

Can my old dry chemical system stay?

Dry chemical systems don't meet UL 300. Ask the Fire Prevention Division whether yours must be replaced; if so, we install a new wet chemical system.

Do I need a Class K extinguisher too?

Yes. Kitchens with a suppression system also need a Class K portable extinguisher.

Plan your Ventura hood suppression install

(213) 568-0188 or socal@1profire.com

New kitchen in Ventura?

(213) 568-0188