Is the hydrant on Ventura Water's system or yours?

Ventura Water is the utility the City of Ventura runs. The hydrants this page covers are a different thing. They sit on a private fire service main serving your property, and the owner of that property is responsible for keeping them in working order year after year. NFPA 24 covers those private mains and their fittings. Unsure? Check your site drawings, or ask Ventura Water, before you book.

At the hydrant: the yearly flow test and inspection

NFPA 25 calls for every private hydrant to be flow tested and inspected once a year. A visit usually goes like this:

  1. We check the barrel, caps, outlet threads and operating nut for damage, leaks or missing parts.
  2. A static pressure reading comes first, before any water moves.
  3. Then we open the hydrant fully and take a residual reading during flow, following NFPA 291.
  4. It flows until the water runs clear.
  5. We close it slowly, so the main doesn't take a pressure surge, and confirm it shuts off tight with no leaking at the outlets or base.
  6. NFPA 291 also sets the bonnet color code by flow class, so we note whether the paint on your bonnet matches what the hydrant actually delivered.

If a part fails, it goes on the list for fire hydrant repair in Ventura. Routine upkeep between tests falls under fire hydrant maintenance.

Fire Prevention at the Ventura Fire Department

The City of Ventura has its own fire department. It is separate from the Ventura County Fire Department. Its Fire Prevention Division reviews construction plans and carries out fire safety inspections within the city, and you can reach it at 805-658-4717. Ask them what hydrant test records they expect you to keep. Local fire rules live in Chapter 14.10 of the San Buenaventura Municipal Code, which adopts the California Fire Code along with the city's own amendments. Editions change. Confirm which one applies to your building.

Licensed contractor, and booking a Ventura visit

California work for 1 Pro Fire is done by Hedrick Fire Protection. Hedrick holds C-16 and C-10 contractor licenses and is licensed by the California State Fire Marshal under Title 19 for inspection, testing and maintenance of water-based fire protection systems. To book, call (213) 568-0188 or email socal@1profire.com. Tell us the address and how many hydrants are on site. We'll give you dates.

The same property may also have other water-based systems: see fire sprinkler service in Ventura and our Ventura fire protection services page. For sites elsewhere in the region, see annual hydrant testing in Ventura County, Los Angeles County and Orange County.

Questions Ventura callers ask about hydrant tests

Will you come to a hospital location in Ventura?

Yes. Hospitals with private hydrants get the same annual test as any other property, so send the address and the number of hydrants and we'll set a date.

How often do you service the Ventura area?

We schedule Ventura visits on request. Send your address and we'll give you dates.

Does a hydrant repair count as the annual test?

No. A repair fixes a fault. The yearly flow test and inspection still has to happen.

Is the Ventura County Fire Department involved?

It's a separate county agency. For a City of Ventura address, the city's Fire Prevention Division is the office to ask; outside city limits, confirm with the local fire marshal.

Schedule a hydrant test in Ventura

(213) 568-0188 or socal@1profire.com

Questions about a private fire main? Reach us here.