Grease, heat and the heads above your cook line
Restaurants are hard on sprinklers. Grease vapor escapes the hood and settles on heads in the kitchen, and sometimes out in the dining room too. A weekend repaint leaves a coat of paint on a head. Someone adds a tall shelf in dry storage. Any of these can change how a head responds in a fire.
In Simi Valley, the Ventura County Fire Department's Fire Prevention Bureau does ongoing inspections of businesses, in addition to its plan review and new-building work. If an inspector walks your restaurant and asks about the sprinkler system, you want current tags and a recent inspection report on hand. That's what this service gives you.
Restaurant sprinkler testing: what we check and what we run
An inspection looks. A test operates. Most visits do both, and on a typical restaurant system that means:
- Checking heads in the kitchen, dining room, storage areas and restrooms for grease, paint, corrosion, damage or anything blocking the spray.
- Reading gauges and comparing them with earlier readings.
- Confirming control valves are open and secured.
- Flowing water through the test connection to prove the waterflow alarm sounds (and that the monitoring signal goes out, if your building is monitored).
- Running a main drain test so supply pressure can be compared against past results.
- Checking the fire department connection for caps, damage and clear access.
Heads loaded with grease or paint aren't wiped off. They get replaced. If anything fails, you'll know what it is and what the fix involves. Repairs go through our restaurant sprinkler repair service in Simi Valley.
The schedule your system runs on
NFPA 25 sets the cycle. Inspections happen quarterly. Inspection and testing happen annually. Every five years the pipe gets an internal assessment, and gauges are replaced or tested. On top of that, California's Title 19 requires a 5-year service and certification by a contractor licensed by the State Fire Marshal. Skip a cycle and the gap shows on paper.
Has your space housed one restaurant after another for decades? Find out when the heads went in, because NFPA 25 requires heads in service for 50 years to be replaced or sample-tested.
Your sprinklers and your hood system are separate
A hood service doesn't cover your sprinklers. It's easy to mix them up, since both protect the kitchen and both carry tags. The wet chemical system over your fryers and griddles follows NFPA 96 and NFPA 17A and is inspected every six months, on its own schedule. Hedrick Fire Protection is also licensed to install and service commercial kitchen hood suppression systems, so you can book that through our Simi Valley fire kitchen service. Your kitchen also needs a Class K extinguisher, which is covered under fire extinguisher annual certification.
Who may do the work
In California, 1 Pro Fire's work is performed by Hedrick Fire Protection, which holds C-16 (fire protection) and C-10 (electrical) contractor licenses and is licensed by the California State Fire Marshal under Title 19 to inspect, test and maintain water-based fire protection systems, including the 5-year certification.
Book a restaurant sprinkler inspection
Call (213) 568-0188 or email socal@1profire.com. Before you call, find the date of your last inspection report. Tell us how many locations you run. If you know whether the building has alarm monitoring, mention that too, because it changes how the waterflow test gets coordinated.
Restaurant sprinkler inspection questions
How often does a restaurant sprinkler system need inspecting?
Quarterly and annually under NFPA 25, plus a five-year internal assessment and California's five-year Title 19 certification. The hood system is separate.
Is restaurant sprinkler testing the same as an inspection?
No. An inspection is a visual check of heads, gauges, valves and connections, while testing actually operates parts of the system, such as the waterflow alarm and the main drain. Most annual visits include both.
Who inspects restaurants for fire code in Simi Valley?
The Ventura County Fire Department's Fire Prevention Bureau does ongoing inspections of businesses. The county fire code in effect since January 1, 2026 adopts the 2025 California Fire Code, so check any specific requirement with the Bureau.
Can a greasy sprinkler head just be cleaned?
Usually not. Under NFPA 25, heads loaded with grease or paint are replaced.