Which extinguishers are due for a hydro test
Every portable extinguisher has a pressure shell. Hydrostatic testing proves it can still hold pressure safely. The interval depends on the agent inside:
- Dry chemical (the ABC unit on most walls): every 12 years.
- CO2: every 5 years.
- Water: every 5 years.
- Wet chemical (Class K, the kitchen unit): every 5 years.
One date trips people up. Stored-pressure dry chemical units also get a 6-year internal maintenance, a teardown that is a separate service from the hydro test that comes due at year twelve, so a unit can pass its teardown and still need testing later.
Where to find the last test date
Look at the cylinder. On low-pressure units such as dry chemical and water extinguishers, a past hydro test is usually recorded on a label on the shell, showing the month and year of the test and who did it. No label? Start from the manufacture date printed on the unit, because the first test is counted from the year the cylinder was made.
CO2 and other high-pressure cylinders are different. Their test dates are stamped into the metal near the neck. The annual service tag on the collar is a separate record. Check each unit. A building with many extinguishers rarely has them all on the same year.
What happens to a cylinder during the test
The technician empties the extinguisher, removes the valve and inspects the cylinder inside and out for corrosion, dents and damaged threads before any pressure goes on. Then the shell is filled with water and pressurized.
Low-pressure shells get a proof test. They pass if they hold pressure with no leaks, bulges or distortion. High-pressure cylinders such as CO2 go into a water jacket that measures how far the shell stretches under pressure and how much of that stretch remains once the pressure comes off. Too much permanent stretch fails it.
A failed cylinder comes out of service. A passing one is dried, recharged with fresh agent, labeled with the new test date and returned to its bracket so it's ready for the next monthly check.
Who checks the dates in Saticoy
Overdue hydro dates tend to surface during a fire inspection. In Saticoy, who does that inspection depends on your parcel: in unincorporated Old Town Saticoy it's the Ventura County Fire Department's Fire Prevention Bureau, and in the larger part of Saticoy annexed into the City of Ventura it's City of Ventura Fire Department inspectors. Not sure which applies? Check whether your parcel sits in unincorporated Old Town. Extinguisher rules in California are in Section 906 of the California Fire Code.
Who does the testing
California requires a State Fire Marshal licensed firm and technician for extinguisher service under Title 19. Our California work is done by Hedrick Fire Protection, which holds C-16 and C-10 contractor licenses and is licensed by the State Fire Marshal under Title 19 for extinguisher service and for water-based system service.
To book testing, call (213) 568-0188 or email socal@1profire.com. A rough count of units by type helps.
Hydrostatic testing questions
Can a disposable extinguisher be hydro tested?
No. Non-rechargeable units aren't built to be emptied and refilled, so they're replaced when they come due.
Does our monthly extinguisher check cover this?
No. A monthly visual check confirms the unit is in place, charged and undamaged. It can't show whether the shell will still hold pressure; only a hydro test does that, which is why the two schedules run side by side.
Does sprinkler pipe get a hydrostatic test too?
Yes. New sprinkler piping gets a water pressure test before the system goes into service, as part of installation. See our Saticoy fire sprinkler installation page.