Skip to main content

Sprinkler repair for kitchens, dining rooms and walk-ins · City of Los Angeles

What breaks in a restaurant sprinkler system

Kitchens are hard on sprinkler heads. Grease and cooking vapor settle on the heads over and around the line, and a head coated in grease or paint can be slow to open when heat reaches it. Those heads get replaced. They don't get scrubbed and put back. This page covers repair work in the City of Los Angeles.

Common restaurant repairs:

  • Heads knocked crooked by carts, ladders or shelving in storage rooms and walk-ins.
  • Leaks and corrosion at fittings, often above a ceiling where a water stain shows first.
  • Missing escutcheons or open ceiling tiles after a remodel, which can let heat escape past a head and slow its response.
  • Heads blocked by signs, shelving or equipment added after the system went in.
  • Heads in service 50 years, which NFPA 25 says must be replaced or sample-tested.

The right replacement head

A new head has to match the old one in temperature rating, response type, orifice size (the K-factor) and orientation, or it may not work the way the system was designed to. Heads near cooking equipment often carry a higher temperature rating than heads in the dining room. Mixing them up is easy. Check your spare-head cabinet, too. It should hold spares of each head type in the building, plus the wrench that fits them.

Who enforces sprinkler rules in Los Angeles

Inside city limits, the Los Angeles Fire Department's Fire Prevention Bureau handles fire marshal duties and fire code enforcement for businesses, with units that include Industrial and Commercial and Public Assemblage. Plan work is a separate office. LAFD Fire Development Services, part of the One Stop Permit Center, runs plan review, permit approvals and field inspections for new construction. Moving or adding heads in a remodel? Ask that office whether plans are needed before the work starts.

Who does the work

Our California work is performed by Hedrick Fire Protection, which holds C-16 (fire protection) and C-10 (electrical) contractor licenses and is licensed by the California State Fire Marshal under Title 19 for work on water-based fire protection systems. The electrical license counts when a repair touches the waterflow or tamper switch wired to your alarm panel. Panel trouble? See our Los Angeles fire alarm repair page.

Your hood system is separate. That wet chemical system gets inspected every six months; see kitchen hood suppression service in Los Angeles, and fire extinguisher service for the Class K extinguisher a suppressed kitchen also needs.

To book a repair, call (213) 568-0188 or email socal@1profire.com. Tell us where the head is (kitchen, dining room, walk-in or storage) and attach a photo if you can.

Outside city limits? See restaurant sprinkler repair in Los Angeles County or in Orange County, or browse every service on our Los Angeles fire protection page.

Restaurant sprinkler repair questions

Some heads already need adjusting, and an earlier construction crew installed the system with no handoff. Can you help?

Yes, on the repair side. A technician can fix the heads you already know about and point out other damage they see while on site. Whether the original install matched approved plans is a question for LAFD Fire Development Services, which handles plan review and field inspections for new construction.

Can a greasy kitchen head be cleaned?

No. A head loaded with grease or paint is replaced with a matching head.

Is the hood system part of a sprinkler repair?

No. It's a separate wet chemical system with its own six-month inspection cycle.

Our address says Los Angeles, but we're in East LA or Commerce. Who is our fire authority?

Parts of East Los Angeles and Commerce (ZIPs 90022, 90023 and 90040) sit outside the city and outside LAFD territory, so start with the Los Angeles County Fire Department. In Vernon, where ZIP 90058 is shared with the city, confirm with the fire authority for your exact address. We can do the repair either way.

Our services include

Fire Kitchen System Installation
Restaurant Hood Systems Service

If a head is leaking or went off

Fire showing? Call 911 first.

If there's no fire and water is still running, the flow stops only when someone closes the system's control valve. A closed valve leaves the building with no sprinkler protection, so tell the fire department, post someone to walk the space and watch for fire, and reopen the valve as soon as the head is replaced.

Then call us. Say a head is leaking, and we'll book the earliest visit we have.

(213) 568-0188 or socal@1profire.com

Restaurant sprinkler repair in Los Angeles

(213) 568-0188