Covina's fire inspectors work out of Citrus Avenue
Covina has no city fire department. The Los Angeles County Fire Department covers the city 24 hours a day from Station 152 on W. Cypress Ave. and Station 153 on E. Cypress Ave. Inspections run from a different desk. Business fire inspections in Covina are handled by the county's Fire Prevention East Region office at 400 N. Citrus Ave., in Covina itself, and the request line there is (626) 974-8335.
Not sure how to report finished work? Call that office and ask. We do the testing and tagging; the inspector decides what passes.
Extinguishers: what most Covina calls are about
All of our Covina calls so far have been about fire extinguishers. Owners ask about annual tags, about one new unit for an apartment, and whether an extinguisher last serviced decades ago can still be saved. Recent Covina quotes ran $35 per extinguisher for annual certification and $80 per unit when replacing makes more sense than certifying.
The calendar looks like this:
- Monthly: a quick visual check by you or your staff.
- Yearly: maintenance by a licensed technician, recorded on the tag.
- Every 6 years: internal maintenance (a teardown) for stored-pressure dry chemical units.
- Hydrostatic test: every 12 years for dry chemical, every 5 years for CO2, water and wet chemical (Class K) units.
Tags lapse every year. California requires this work to be done by a firm and technician licensed by the State Fire Marshal. Ours is done by Hedrick Fire Protection, which holds C-16 (fire protection) and C-10 (electrical) contractor licenses and is State Fire Marshal licensed under Title 19 for extinguisher service and for inspection, testing and maintenance of water-based systems.
More detail: extinguisher annual certification in Covina, extinguisher refills and recharges, hydrostatic testing and staff extinguisher training.
Fire system service in Covina
Fire system service means the fixed systems in your building. Each runs on its own clock.
Sprinklers
Sprinkler inspection, testing and maintenance follow NFPA 25, with quarterly and annual inspections plus a 5-year internal pipe assessment and gauge replacement or testing. California's Title 19 also calls for a 5-year service and certification by a State Fire Marshal licensed contractor. Old heads count too. Heads in service 50 years must be replaced or sample-tested. Start with fire sprinkler service in Covina, or fire sprinkler installation for new work.
Fire alarms
Fire alarms are inspected and tested at least once a year under NFPA 72. Some devices need it more often. For trouble signals or failed devices, see fire alarm repair; for routine visits, see fire alarm testing.
Kitchen hood systems
Restaurant hood systems get inspected every six months under NFPA 96 and NFPA 17A, and their metal-alloy fusible links are replaced at least that often. Older dry chemical systems don't meet UL 300, the test standard for wet chemical systems over cooking appliances. Add a Class K extinguisher too. Hedrick is licensed to install and service commercial kitchen hood suppression systems. See fire kitchen service and restaurant sprinkler inspections.
Private hydrants and Covina's water providers
The City of Covina Water Division maintains about 1,000 fire hydrants on its own system. We don't service those. Our hydrant work is on private hydrants, the ones on your property fed by a private fire service main, which get an annual flow test and inspection under NFPA 25.
Covina has several water providers. Depending on the address, it may be the city, City of Azusa Light & Water, Golden State Water, Suburban Water Systems, or Valencia Heights Water Company / Covina Valley Water Company, so the provider involved in a flow test depends on where your property sits. Tell us your address first.
Details: annual fire hydrant testing, hydrant maintenance, hydrant repair and hydrant installations.
Covina fire protection questions
Can an extinguisher last serviced in 1992 still be serviced?
It depends on the unit. A technician checks its type, condition and test history, then tells you whether it can be serviced or should be replaced.
What do hydro testing and six-year maintenance add to the annual inspection?
Both are on top of the yearly tag. Stored-pressure dry chemical units need a 6-year teardown and a hydrostatic test every 12 years, while CO2, water and Class K units are hydro tested every 5 years.
How do I notify the fire department once service is complete?
Ask the county's Fire Prevention East Region office at (626) 974-8335. Do it before your deadline.
Does the city maintain fire hydrants in Covina?
Yes, for hydrants on its own system. Private hydrants on your property, fed by your own fire service main, are the ones we test and maintain.
Book service in Covina
Call (213) 568-0188 or email socal@1profire.com with the address, what's in the building and when your tags or inspection come due.
(213) 568-0188 or socal@1profire.com (213) 568-0188Working outside Covina? See our Los Angeles County fire protection page or San Bernardino County fire protection page.