Is your restaurant's sprinkler service current?
Check the tag on your riser. It shows the last service date. If that date is more than a year old, or nobody on staff knows where the riser even is, your system is probably behind on its inspections.
The Eaton Fire burned many of the businesses on Lake Avenue in January 2025. Much of Altadena is still being rebuilt. If your restaurant is reopening after the fire, or moving into a rebuilt space, have the sprinklers inspected and tested before the first dinner service. You want to know they work. Before you need them.
The NFPA 25 schedule for a restaurant system
Sprinkler inspection, testing and maintenance in California follow NFPA 25. Title 19 adds a state rule on top. Here is the calendar:
- Quarterly: inspections of the parts you can see and reach.
- Annually: a full inspection with testing of the system.
- Every 5 years: an internal pipe assessment, gauge replacement or testing, and the Title 19 five-year service and certification, which must be done by a contractor licensed by the State Fire Marshal.
- At 50 years in service: heads are replaced or sample-tested.
Your hood system runs on its own clock. Commercial cooking suppression gets inspected every six months under NFPA 96 and NFPA 17A. Hedrick is licensed to install and service kitchen hood suppression systems, so you can book both with us through our Altadena kitchen fire suppression service.
Restaurant sprinkler testing: what happens on the visit
Inspection means looking. Testing means making the system act. On a typical annual visit the technician opens the main drain to check the water supply, trips the flow alarm to confirm it signals, and turns the control valves so they move freely and are left fully open. Gauges get read. Readings get compared with past ones.
Heads near the cook line
Kitchen heads take a beating. Grease, heat and cleaning chemicals can coat or corrode a head, and a loaded head may not open the way it was designed to when the heat finally reaches it. Staff hang utensils from pipes. Boxes get stacked too high. A remodel crew paints over a head. Each one is a finding.
Anything that fails goes to restaurant sprinkler repair in Altadena.
Who inspects restaurants in Altadena
Altadena is unincorporated. Los Angeles County governs it directly. The Los Angeles County Fire Department answers fire calls here, and its Fire Prevention Division runs annual business inspections through regional units; Altadena falls under the Arcadia office in the department's East Region.
Keep your service tags and reports where you can find them. If you're unsure what the county expects for your occupancy, ask the Fire Prevention Division before your visit.
Who does the work
In California our work is done by Hedrick Fire Protection, which holds C-16 fire protection and C-10 electrical contractor licenses and is licensed by the California State Fire Marshal under Title 19 for inspection, testing and maintenance of water-based fire protection systems.
For the rest of the building, see our fire sprinkler service in Altadena or the Altadena fire protection hub. Restaurants elsewhere can use our Los Angeles County restaurant sprinkler inspections or Orange County restaurant sprinkler inspections pages.
Altadena restaurant sprinkler questions
How often does a restaurant sprinkler system need inspection?
Quarterly and annually under NFPA 25. Every five years, Title 19 also calls for a service and certification by a State Fire Marshal licensed contractor.
Is restaurant sprinkler testing the same as an inspection?
No. An inspection is visual. Testing operates parts of the system, such as the main drain and the flow alarm, and most annual visits include both.
Do you service the public fire hydrant outside my restaurant?
No. We don't service public hydrants. If your property has its own private hydrant, see annual fire hydrant testing in Altadena.
Is the hood suppression system part of the sprinkler inspection?
It's a separate system. It's inspected every six months under NFPA 96 and NFPA 17A.
To schedule a restaurant sprinkler inspection in Altadena, call (213) 568-0188 or email socal@1profire.com
Our services include
Have your last report ready
The date on your riser tag tells us what's due. Read it off before you reach out.
(213) 568-0188 or socal@1profire.com